Cape Town summers put chillers, air handling units and control valves under sustained load. The buildings that cope best are the ones where the building management system was checked before the first heatwave, not during it.

Start with sensor integrity. Space temperature, return air and chilled water sensors drift over time, and a sensor reading two degrees low will quietly hold a plant at full output all afternoon. Compare field readings against a calibrated instrument and correct offsets in the controller rather than in the setpoint.

Next, review your schedules and setpoints. Occupancy patterns change, and many sites still run summer plant on a schedule written for a different tenant mix. Confirm optimum start, night setback and public holiday calendars are current.

Then walk the plant room. Look for valve actuators that no longer stroke fully, dampers stuck in one position, and control panels running hot with blocked ventilation. These are mechanical faults that no amount of software tuning will hide.

Finally, check that alarms actually reach a person. An alarm list nobody reads is the most common reason a small fault becomes a shutdown. If your critical alarms are not routed to a monitored inbox or phone, fix that before the season starts.